Facilities provided, accessible, clean, good repair |
No |
No
|
No |
REPEAT:
.1312 (a) All institutions shall provide toilet, handwashing, and bathing facilities that are available for use by residents and staff. These facilities shall be kept clean and in good repair.- Observed slow draining at hand sink in the room 311, 501, 608, 707, 800/700 restroom hallway, women restroom main hallway. Observed disrepair faucet in 808, loose toilet seat in women restroom main hallway. Repair needed. Ensure to keep hall hand sinks in good repair. |
|
16
|
3
|
Hot water between 105°F and 116°F |
No |
No
|
No |
REPEAT
.1313 (d) Institutions shall provide water heating facilities. Hot and cold running water under pressure shall be provided to carry out all operations. Hot water shall be provided at temperatures between 105 degrees Fahrenheit and 116 degrees Fahrenheit at handwashing and bathing facilities. Observed hot water temperature measured at 132F in woman/men restroom main hallway, 130 in men restroom main hallway and room 301, 117F in room 105, 125F in room 212, 118F in service hallway sink, 119F in room 202, 128F in room 311, 124F in room 406, 125F in room 212, 104F at sink in 500/600 hallway, 101F in room 501/508/704/707, 99F in room 608. Provide tempered water range between 105- 116F at anytime. |