7
|
0
|
Facilities provided, accessible, clean, good repair |
No |
No
|
No |
General Comment:
.1312 (a) All institutions shall provide toilet, handwashing, and bathing facilities that are available for use by residents and staff. These facilities shall be kept clean and in good repair.- Observed slow draining at hand sink in the room 808, 706, 405, 106, 209. Observed loose/disrepair faucet in 407, staff break room 100-200 hallway, and rehab room. Repair needed. Ensure to keep hall hand sinks in good repair. |
|
10
|
0
|
Handwashing facilities properly located and equipped |
No |
No
|
No |
General Comment:
.1312 (d) Handwashing facilities shall be supplied with soap and disposable towels or hand-drying devices.- Observed in all med room hand sinks. At least one of the two soap and paper towels dispenser is working. Maintenance director stated, the facility is changing out a new type of dispenser. While doing that, please ensure all hand sinks are supplied with soap, paper towels and running water for proper hand washing at all time. |
|
16
|
3
|
Hot water between 105°F and 116°F |
No |
No
|
No |
REPEAT
.1313 (d) Institutions shall provide water heating facilities. Hot and cold running water under pressure shall be provided to carry out all operations. Hot water shall be provided at temperatures between 105 degrees Fahrenheit and 116 degrees Fahrenheit at handwashing and bathing facilities. Observed hot water range between 118F -132F. The hottest temperature at 132F in the salon and that hallway. 118F- 123F (back hallway, 407, 405, 308, 106, restroom front hallway, 808, 706, 508. Ensure to provide hot water temperature range between 105- 116F. |