3
|
2
|
Walls and ceilings cleanable, clean, good repair |
No |
No
|
No |
REPEAT
Keep all walls and ceilings clean and in good repair. 15A NCAC 18A .1310. Observed walls inside (600 hall) equipment storage room with heavy damage in need of repair; Observed walls inside resident room #603 with wall scuffs in need of touch-up paint. |
|
13
|
1
|
Lavatory and bathing hot water between 100 and 116 F |
No |
No
|
No |
Maintain the hot water at all resident accessible handwashing sinks and bathing facilities within the temperature range of 100°F to 116°F. 15A NCAC 18A .1312 (e). Observed half of the facility having hot water at hand washing sinks inside residents rooms measuring above 116F (118F) and the other half of the facility measuring too low (90-95F) at hand sinks. |