5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Log book not maintained daily for May/June/July. Missing periodic days. Ensure daily record keeping for chlorine, pH and main drain checks.
CYA recorded at 100 ppm. EHS measured 50 ppm. Ensure accurate record keeping.
One reagent of DPD-2 expired and some reagents expiring in July. Replace as needed. |
|
10
|
2
|
Pool maintenance: safety ropes with floats and contrasting color bands provided at shallow area breakpoints |
No |
No
|
No |
Safety divider rope with damaged buoys. Replace rope.
.2523(e) Provide a minimum of 3/4 inch diameter safety rope at the breakpoint.
.2523(e) Safety rope shall be marked with colored floats, 5 ft. apart or less. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Step handrail loose at upper section. Tighten handrail. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Some seal/grout missing between coping and pool deck pavers at deep end ladder. Repair so impervious surface. Intent to Suspend issued. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
No flow meter on chlorinator inlet. Original construction. If repaired/replaced, ensure flow meter installed per mfg. instructions. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Small leak at return line from multi-port. Repair leak.
Flow meter not reading. Flow restriction at 80 gpm due to number of returns. Intent to Suspend issued.
Flow meter not installed per mfg. instructions. Pump is not variable speed pump and facility is controlling flow through the flow meter with a valve. If pump changed, a 10% accurate flow meter shall be installed per mfg. instructions for pump approval. Blue White F-300 flow meter requires 5x pipe diameter on the inlet pipe and 2x pipe diameter on outlet (10" inlet and 4" outlet), if replaced. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No hose bib in restrooms. Provide hose bib within 50 ft. Original construction.
Partitions in restrooms go to floor with no place for drainage. Original construction. Floor drain in center restroom stall. Floors shall be built to slope to drain and drain adequately.
Could not view men's restroom at time of inspection. |