| CDI=Corrected During Inspection | |
R=Repeat Violation | |
VR=Verification Required | |
|
|
| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Cyanuric acid recorded as 100 ppm daily. When verified, reading at 70 gpm. Record cyanuric acid weekly.
Some days missing from logs. Ensure daily record keeping for chlorine, pH and main drain checks. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Leaf covering main drain screw. Moved during the inspection. Ensure cleaning as needed to keep pool floor clean and drains clearly visible. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
One skimmer full of debris. Emptied during the inspection. Ensure skimmers cleaned as needed so that skimmers functioning per NSF approval. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Step handrail loose. Keep in good repair. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Table/chairs near ring buoy within 5 ft. of pool edge. Maintain 6 ft clearance around the pool in all locations. Intent to Suspend issued. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
No flow meter on chlorinator inlet. Original construction. If repaired/replaced, ensure flow meter installed per mfg. instructions. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Leak at pump around casing. Repair leak. Intent to Suspend issued. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
One toilet seat loose in women's restroom. Keep fixtures in good repair.
No hose bib in restrooms. Provide hose bib within 50 ft. Original construction.
Partitions in restrooms go to floor with no place for drainage. Original construction. Floor drain in center restroom stall. Floors shall be built to slope to drain and drain adequately.
Could not view men's restroom at time of inspection. |
|