2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Pool chlorine at 0 ppm. Maintain at least 1.0 ppm through the chlorinator. Immediate Suspension issued. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Cyanuric acid at 100 ppm which is max for CYA. Lower to below 100 ppm. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Skimmer in deep end of swimming pool not operational. Pool square footage is 740 sq ft per records. Only two skimmers required per rules. Continue to monitor. If floating debris becomes an issue, pool may be required to repair. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Ring buoy not accessible due to landscaping. Move to accessible location. Immediate Suspension issued. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Paver chipped at deep end. Secure to paver. Does not appear sharp at time of inspection. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Phone not ringing pool deck or back to front desk. Phone number posted must ring directly to pool deck or to front desk who is monitored 24 hr/day. Immediate Suspension issued. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Digital flow meter operable but exceeding permit restriction of 100 ppm. Limit flow so that flow meter reading max of 100 ppm or less. Flow must be correct for permit to be re-instated.
No spare pump basket for pump. Provide spare pump basket |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Mirrors in restroom could not be verified as shatterproof. Mirrors shall be shatterproof. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No hose bib in restrooms. Provide hose bib within 50 ft. Original construction. |