6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Main drain cover recalled cover. Has WAV12xxx installed. PDSC form submitted is incorrect. Paperwork indicates a 1216xxx. Replace cover with approved cover and resubmit paperwork. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Some chipping paint on pool walls. Keep in good repair. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Equalizer line cover not flush to wall. Provide no greater than 1/2" between wall and cover. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Deep end ladder loose. Keep in good repair. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Observed pushbar exit measuring 52" from ground to bottom of pushbar at lobby entrance. Raise to 54" measured from ground. Observed meshing on fence greater than 1/2" x 1/2". Provide no openings greater than 1/2" within 18" of gate latch mechanism. Additional clarification from the State has resulted in changes to how current code is enforced from previous inspections. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Pool furniture 5 ft to pool. Maintain 6 ft clearance. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Drain in backwash pit not cut flush. Cut flush to pit floor to eliminate holding water. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
No backflow prevention on hose bib in pump room. Provide backflow prevention device on all hose bibs. |