Water quality: disinfectant residual provided by |
No |
No
|
No |
Pool chlorine at 0.4 ppm. Maintaint at least 1.0 ppm. Immediate Suspension issued. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Cyanuric acid greater than 100 ppm. Maintain at 100 ppm or less. Record book indicates less than 100 ppm. Tested during inspection. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Drain cover damaged. Replace drain cover. Immediate Suspension issued.
Pump Hayward SP2615x20. Not original pump. Submit updated PDSC form with new pump. Previously installed 1 hp pump. Works with piping installed, drain covers and filter currently installed. Field review done during inspection. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Etching on steps and bench where plaster has worn off to show gunite. Repair steps and bench where needed. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Handrail into pool loose. Keep tight and in good repair. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Ring buoy tied to railing and not accessible. Rope too long. Corrected to 15 ft during inspection and untied. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Opening around skimmer >1/2". Fill opening to prevent hazard.
Deck paver loose at entrance to steps. Repair paver. |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
Could not verify light in pool. Light must be operational for night swimming. Will verify on return visit. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Acid feeder could not be veriifed. Will verify on return visit or after 30 day Intent is issued. Must turn off when pump turns off. |