Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Observed one missing return fitting. Corrected during inspection.
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Observed new gate installed on fence for grill area that leads off of pool dec. Gate locked at time of inspection.
Newly installed gate provides access from outside pool deck to pool deck. Gate previously not regulated that leads from grill area to pool deck is now considered enterence to pool deck and does not meet requirements. Gate from grill area to pool deck has latch below 54" and swings toward the pool.
.2528(a) Gate latches shall be 54" in height.
.2528(b) Gates may only swing toward pool if built prior to May 2010 and natural topography, landscape, or egress prevents the gate from swinging away from the pool.
.2528(a) Gate latches located at less than 54" shall require the use of key, combination lock or card reader or be located on the inside of the gate at least three inches below the top of the gate with no greater than 1/2" within 18" of latch mechanism.
Intent to suspend issued. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Observed one filter pressure gauge not properly functioning.
.2519(k) Provide operational pressure gauge on filter.
Intent to suspend. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Observed pump in structure with only 3 walls.
.2533(a) Pump room shall contain at least all pumps, chemical feeding equipment, and other mechanical and electrical equipment. |