Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Door from clubhouse not latching at time of inspection.
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Operator corrected to self-close, self-latch. |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
Light fixture protruding from wall at time of inspection, creating hazard. .2537(9) Underwater light niches shall be maintained or covered so not to present a hazard. Operator secured light fixture in pool to be flush with pool wall. Corrected. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Observed one inlet missing eyeball fitting. All other inlets in place.
.2518(i) Provide inlet fittings in good repair. Lack of severity does not warrant permit action. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Dry chemicals stored beside and below liquid chlorine at time of inspection.
.2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up. |
|
28
|
2
|
Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted |
No |
No
|
No |
Shower off at time of inspection. .2526(h) Shower(s) shall be provided. |