Premises: emergency telephone provided |
No |
No
|
No |
Emergency phone with incorrect phone number posted on management company signage. Corrected during inspection. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Chlorinator/automated feeder could not be verified to detect flow at time of inspection. On same circuit as pump so when pump turns off, whole system turns off. Intent to Suspend issued.
.2535(6) Automatic chlorine and bromine feeder pumps shall be automatically prevented from operating when the circulation pump is not in operation. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Some chemicals stored in pump room. Keep chemicals in chemical storage room. Corrected during inspection. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Some build-up on showerheads in women's team locker room. Some staining on pool locker room floors. Keep fixtures clean. Water in locker rooms at >110 F. Maintain at 110 or below.
Men's locker room could not be viewed at time of visit due to occupancy. |