Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameQUEENS UNIVERSITY - LEVINE CTR
Address2201 WELLESLEY AVE
 
City/State/ZIP
CHARLOTTE NC 28207
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 12/4/2019
Final Score @ Grade
16
General CommentsChlorinator not verified at time of inspection. Verified on previous inspection. Per operator, no changes. Will be required to verify automated chlorinator and acid feeder for permit inspection. Feeder must detect flow and turn off when no flow.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
5 4 Water quality: daily written records of water quality and test kit kept on site No No No Some days missing temperature logs from previous months. Record temp daily.
11 2 Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair No No No Some diving platforms at 31" from surface level of water. For diving platforms in water greater than 5 ft., provide at no greater than 30" from water level. .2517 Diving equipment shall be installed in accordance with Rule .2517.
17 4 Premises: decks unobstructed, properly drained, free of trip hazards No No No Missing cap for pole hole in decking. Corrected and replaced during inspection. .2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Flow meter stuck. Keep operational. Will be required for permit inspection in spring.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No One sink in both women's locker rooms without soap. Provide soap at each sink. Some staining on flooring under sink areas in both locker rooms. Keep fixtures in good repair. Men's locker room could not be verified at time of inspection due to occupancy.