24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter for filtration pump not operable. No permit restriction. Repair flow meter so operable.
Flow meters for waterfall and jets verified as the following flow meeting permit restrictions - Waterfall at 100 gpm; Jets 1 and 2 at 50 gpm and 40 gpm. Note: Jet 1 flow meter is required to be changed to a 5% accurate flow meter with new PDSC form submitted prior to permit for 2026. If not complete, permit will not be issued. All other flow meters ok. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Bucket of bromine tabs in pump room next to tablet feeder. Store chemicals in chemical storage room. Corrected during the inspection. Bag of dry chemical on chemical storage room floor. Dry chemicals not in waterproof containers shall be stored up off the floor. Corrected during the inspection. |
|
32
|
2
|
Dressing and sanitary facilities: floors smooth, slip-resistant, kept clean |
No |
No
|
No |
Floors in restrooms do not appear to be slip-resistant. Provide slip resistant flooring in restrooms. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No floor drain in restrooms. Original construction. Provide floor drain in restrooms.
No hose bib in restroom. Provide hose bib. Original construction. |