Water quality: pool water pH |
No |
No
|
No |
Spa pH at 6.8. Corrected to 7.4 during the inspection. Maintain pH at 7.2 to 7.8. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Total alkalinity not recorded for last two weeks in December and January. Ensure weekly record keeping for TA. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
No flow meter on chlorinator. If ever replaced, install per mfg. instructions. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meters for jet pumps not working. Both flows are required at 100 gpm. Repair flow meters for permit restriction. Intent to Suspend issued.
Waterfall jet pump not operable. Flow restriction at 100 gpm. Intent to Suspend issued.
Small leak at jet pump. Repair leak. Did not warrant repair at time of inspection. |
|
32
|
2
|
Dressing and sanitary facilities: floors smooth, slip-resistant, kept clean |
No |
No
|
No |
Floors in restrooms do not appear to be slip-resistant. Provide slip resistant flooring in restrooms. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No floor drain in restrooms. Original construction. Provide floor drain in restrooms.
No hose bib in restroom. Provide hose bib. Original construction. |