Water quality: pool water pH |
No |
No
|
No |
Spa pH below 6.8. Immediate Suspension issued. Provide pH at 7.2 to 7.8. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Test kit with black build-up in test tube. Replace test kit. 30 day intent to suspend issued for pool inspection. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
One drain cover not in place on main drain and EQ line cover (plugged and dummy cover) not in place on pool wall - hole in wall. Replace per requirement. Immediate Suspension issued. If new cover replaced, provide updated PDSC form.
.2539(b) All suction outlets shall be protected by anti-entrapment cover/grates in compliance with APSP-7. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Handrail loose on spa. Keep tighten. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Some fittings missing from jets and returns. Replace fittings as needed. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter stuck. Keep operational. Corrected during the inspection. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Muriatic acid stored over bicarb. Store chemicals so not to present a hazard. Corrected during the inspection. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No hose bib or floor drain in pool restrooms. Original construction. Provide hose bib and floor drain. |