Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameHILTON GARDEN INN AYRSLEY
Address1920 AYRSLEY TOWN BLVD
 
City/State/ZIP
CHARLOTTE NC 28273
Premise Type55 - Year-Round Spa
CountyMecklenburg
Inspection Date 5/8/2025
Final Score @ Grade
8
General CommentsLifted suspension for water quality and conducted inspection. FlowVis installed, hard to read. Permit restriction of no greater than 55 gpm (+/-) 5%, starts at 70 gpm, reads less than this, about 60 gpm. Timer could not be verified on jet pump. Feature pump exceeds drain cover flow. Requires a true flow reading and submittal of new PDSC form with flow reading for approval. Flow shall not exceed 100 gpm. Current piping does not appear to have the required 11" for FlowVis or other types of flow meter. A properly installed flow meter accurate to 5%-10% shall be installed. Pool may open without the jets functional. Currently turned off in pump room. Issued local permit sticker. Permit restriction that jets must remain inoperable until drain cover issue is addressed. “A” Open for Business

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No Doors propped open onto pool/spa deck at time of inspection. .2537(b) All gates and doors shall be self-closing, self-latching and be closed when not in use. Closed and corrected.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Observed standing water on pump room floor. .2533(d) Pump room floor shall be kept dry and free of standing water. Light not working in chemical storage room. .2534(6) Provide sufficient lighting in chemical storage room. Inadequate ventilation in pump room. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. Inadequate ventilation in chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Hot water in restrooms over 110 F. .2526(i) Water in restrooms shall not exceed 110 F.