3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
Observed pH below 6.8 during inspection.
.2535(1) Maintain pH at 7.2 to 7.8. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Observed main drain screws rusted.
.2539(d) All drain covers shall be kept in good condition. Missing, broken, or cracked fittings shall be replaced or reattached before the pool should be used. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Observed eye fitting missing on return next to light.
Observed one loose jet fitting on wall with skimmer.
.2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. |
|
14
|
4
|
Pool maintenance: spa timer working properly |
No |
No
|
No |
Observed spa timer exceeding 15 minutes. Corrected during inspection.
.2537(b) Spa times shall not exceed 15 minutes without manual resetting. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Observed door from excersice room not self latching.
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Observed sand filter leaking
.2519 Keep filter in good repair.
Observed flow meter not functiooing.
.2518(g) Keep flow meter operational. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Observed hot water in restroom at womans hand sin at 127F.
.2526(i) Water in restrooms shall not exceed 110 F. |