2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
G.S. 130A-2(3) Chlorine bleached out test kit. Imminent Hazard to public. Lower to measurable level. |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
pH 6.8 at time of inspection. .2535(1) Maintain pH at 7.2 to 7.8.
*Immediate suspension item. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Total alkalinity not recorded weekly. Record weekly.
SVRS on both filtration and feature pumps. Drains are less than 36" apart. Requires monthly testing per mfg. instructions. Record in log book.
Cyanuric acid over 200 ppm, should not be in indoor spa.
.2535 (4) Lower and maintain cyanuric acid at or below 100 ppm.
Permit item |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
No 3' clearance around piping. Floor not sloped to drain. Chemicals in pump room. Pool built 2001. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2533(d) Pump room floor shall be sloped to drain.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Water over 110 F in restrooms.
.2526(i) Water in restrooms shall not exceed 110 F. |