Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameDRURY INN & SUITES SPA
Address415 W W T HARRIS BLVD
 
City/State/ZIP
CHARLOTTE NC 28262
Premise Type55 - Year-Round Spa
CountyMecklenburg
Inspection Date 11/3/2022
Final Score @ Grade
12
General CommentsInspection conducted with inspector Hannah Howard and CPO Steven Hoyt. Labels not observed on spa pumps. Verified that pumps are Sta-Rite pumps with 2 HP motors. Spa jets currently not working. Issue with pump motor. If motor replaced, will need an electrical permit and passing inspection from Mecklenburg County Code Enforcement. Was not able to test spa jets. Ensure that jets shut off within 15 minutes of activation. Intent to suspend issued 24)

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
22 6 Premises: emergency telephone provided No No No Emergency phone number does not match what 911 has. .2530(f) Signage with legible letters providing dialing instructions, address of pool and pool telephone number shall be posted at the emergency phone. - Corrected.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Flow meter stuck. .2518(g) Keep flow meter operational. - Intent to suspend item.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Leaky valve near spa heat exchanger. .2533(d) Pump room floor shall be kept dry and free of standing water.