Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
Jet pump observed is Pentair Challenger CHII-NI-3/4FE not CHII-NI-3/4F, as indicated on PDSC form. Operator stated this pump has not been changed. Updated PDSC form to reflect correct pump and approved. F and FE model are same pump curve. Corrected. .2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Emergency phone not visible from spa area. .2530(f) Provide signage with location of emergency phone if not visible from all areas inside pool enclosure. Operator posted signage with emergency phone location. Corrected. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Pump equipment up ladder, no 3' clearance. Chemicals stored in pump room. Pool built 1984. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water over 110 F in restrooms. .2526(i) Water in restrooms shall not exceed 110 F. |