Water quality: pool water pH |
No |
No
|
No |
pH < 6.8. .2535(1) Maintain pH at 7.2 to 7.8. - Corrected to 7.2. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No records for this past weekend. No recent TA, CYA, or maintenance records. No place for main drain checks. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, and pool water maintenance. Left copy of state log sheet. - Intent to suspend item.
Most test kit reagents have expired. .2535(10) Provide test kit capable of measuring disinfectant level, pH, cyanuric acid and total alkalinity. - Intent to suspend item. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Missing three of six weirs. .2518(k) Provide functional weirs. - Corrected.
Skimmer baskets with leaves. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. - Corrected.
Skimmer baskets cracked. .2518(k) Replace missing or damaged skimmer basket. - Corrected. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Gate at top of ramp by office with 3” gap under gate. .2528(a) Maintain 2" or less under fence and/or gate. - Intent to suspend item.
Gate at top of ramp with < 45” between horizontals. .2528(a) Horizontals shall not be located less than 45" in height. - Intent to suspend item.
Pre-2010 fencing < 48” high in places. .2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Bobber in flow meter upside down. .2518(g) A flow meter, reading in gallons per minute shall be installed per manufacturer instructions. - Intent to suspend item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Hose and umbrella stored next to pool equipment. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Fan not working in chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
Fan not working in pump room. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. |