| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Pool chlorine at 0.4 ppm. Chlorinator turned up during inspection but did not effect chlorine. Verify no blockage. Maintain chlorine at least 1.0 ppm through chlorinator. Immediate Suspension issued. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Daily record keeping not maintained. Maintain daily record keeping for chlorine, pH and main drain/equalizer line cover checks. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Some build-up on wall depth markers. Still visible. Continue to monitor and clean as needed when not visible.
Tile missing from wall in one location. Replace tile. Keep in good repair. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Some skimmer baskets full of debris. Emptied during inspection. Keep baskets free of debris so filtration system can work correctly. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Ring buoy grab rope degraded and not in place/broken. Rope for ring buoy at 37 ft. Required 39 ft. Provide USCG approved ring buoy with 39 ft. rope. Immediate Suspension issued. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
One patio missing fencing. Per operator, fencing will be repaired this week.
Doors into restroom area not self-latching, self-closing. Repair to self-latch, self-close.
Windows shall remain fixed at 4" openings or less. Could not access resident rooms due to covid. Ensure windows affixed at 4". |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
One lounge chair within 6 ft. of pool. Maintain clearance around pool. Corrected during inspection. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter stuck when pump turned off. Keep flow meter operational. Repair. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restrooms >120 F. Maintain at 110 F or below.
No soap in men's restroom. Provide soap.
Note: One toilet running in women's restrooms. Keep fixtures in good repair. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
Blue hose spigot on pool deck without backflow prevention device. Noticed two devices on red hose spigot on deck. Provide backflow prevention device on all hose bibs. |