| CDI=Corrected During Inspection | |
R=Repeat Violation | |
VR=Verification Required | |
|
|
| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Pool tiles dirty. Clean regularly.
Pool floor and benches dirty. Clean regularly. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Two of six skimmers missing weirs. Install functional weirs.
Some baskets full, clean regularly. Corrected by operator. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Ladder loose. Maintain secure and in good condition. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Missing one inlet fitting. Provide functional directional eyeball fittings. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Foothold at brick wall. Maintain fencing at least 48" high.
Push to exit and panic bars < 54" Maintain at 54" or greater. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Deck chipping at handrail. Maintain deck smooth and in good condition.
One chair too close to pool edge. Maintain at least 6 feet of clear walkway around the pool. Corrected.
General Comment: Offset between sections of coping at corner of the pool. Maintain pool deck free of trip hazards. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter reading 160-170 gpm. Pump has a design flow of only 120 gpm. Replace flow meter with a flow meter that is capable of measuring flow to within 10 percent of true flow. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemicals stored in the pump room. Store chemicals in the chemical storage room.
Fan not functioning in the chemical storage room. Provide functional fan.
One light burned out in pump room. Provide adequate lighting. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restrooms 130F. Maintain at 110F or less. |
|