NameWESLEY VILLAGE APARTMENT HOMES
Address2715 WET STONE WAY
 
City/State/ZIP
CHARLOTTE NC 28208
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 8/1/2013
Final Score @ Grade
32
General CommentsImmediate Suspension issued for #2, #3, and #22. Once corrected, contact Katie at 704-309-5494 or Tim at 704-507-6808 to re-open (8/2 through 8/5).

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
2 6 Water quality: disinfectant residual provided by No No No Observed chlorine at 0.8 ppm. Provide at least 1.0 ppm. Immediate Suspension issued.
3 6 Water quality: pool water pH No No No Observed pH at 8.2. Maintain at 7.2 to 7.8. Immediate Suspension issued.
7 4 Pool maintenance: pool walls and floor kept clean, free of debris and in good repair No No No Observed pool floor with debris and some wall depth markers with build-up. Keep walls and floor clean.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Observed 3 of 6 skimmers without weirs. Replace weirs.
22 6 Premises: emergency telephone provided No No No Observed emergency phone not operable. Keep operational. Immediate Suspension issued.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Observed pump leaking and flow meter stuck. Repair leak and keep flow meter operational.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Observed chemicals stored on floor. Store up off floor. Observed pump room floor wet. Keep dry. Observed fan in chem room not continuous. Tied to light. Provide continuous forced ventilation.