Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2528(a) Ground level windows shall not open greater than 4" on to pool deck or child protected by audible alarm. Window in office that opens directly onto pool deck limiting screw removed - window opens greater than 4”. Corrected during inspection.
.2537(b) All gates and doors shall be self-closing, self-latching. Gate on right side fence area not latching closed.
.2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Entry doors from office onto pool deck not fully closing resulting in alarm not operating. Corrected during inspection.
*permit item - 30 day intent to suspend issued for gate not self closing/latching
Fence by pump room and fencing by side gate less than 48" in height due to landscaping and mulch. Horizontals on gate and fence 44". Pool built 2000. .2528(a) Pool fence shall be at least 48" in height measured from outside of barrier..2528(b) Horizontals shall not be located less than 45" in height. No permit action. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Less than 3’ walking space around equipment in pump room. Pool built '00. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2533(d) Pump room floor shall be kept dry and free of standing water. - standing water on pump room floor. |