Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Gate not latching at time of inspection. .2537(b) All gates and doors shall be self-closing, self-latching. Fence by pump room and fencing by side gate less than 48" in height due to landscaping and mulch. Horizontals on gate and fence 44". Pool built 2000. .2528(a) Pool fence shall be at least 48" in height measured from outside of barrier..2528(b) Horizontals shall not be located less than 45" in height.
Operator corrected gate to self-close, self-latch. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Some items stored around piping and equipment in pump room. Some chemicals in pump room. Water on pump floor. Pool built '00. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2533(d) Pump room floor shall be kept dry and free of standing water. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
No air gap at backwash. Pool built 2000. .2513(b) Filter backwash shall be discharged through an air gap. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
No paper towels in men's restroom. Provide hand drying. |