8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
2 of 6 weirs missing at time of inspection .2518(k) Replace missing weirs. Will verify on return visit. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Two rubber stoppers observed missing on ladders. One ladder loose. .2521 Install ladders per manufacturer instructions. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Fence by pump room and fencing by side gate less than 48" in height due to landscaping and mulch. Observed one gate hinge broken, not self-closing, self-latching. One glass door not alarmed or latching at time of inspection. .2528(a) Pool fence shall be at least 48" in height measured from outside of barrier. .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. .2537(b) All gates and doors shall be self-closing, self-latching.
*30 Day Intent to Suspend (ITS) item. Contact Marie Daley at 704-507-6806 when in compliance to lift ITS |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Coping by 3 FT depth markers, on both sides, loose, cracked and chipped more than 1/2". .2537(3) There shall be no loose coping.
.2537(2) Decks shall be kept free of trip hazards or offsets greater than 1/2" due to deterioration or changes from original deck profile.
*30 Day Intent to Suspend (ITS) item. Contact Marie Daley at 704-507-6806 when in compliance to lift ITS |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Some items stored around piping and equipment in pump room. Pool built '00. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. |