Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameEDGE, THE
Address1300 VARSITY LN
 
City/State/ZIP
CHARLOTTE NC 28262
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 8/28/2013
Final Score @ Grade
32
General Comments17 - General Comment: Observed fill spout 6 1/2" to ladder. Over the rim portion moved to <6" from ladder. Immediate Suspension issued for #22. Once corrected, contact Katie at 704-309-5494 to re-open pool.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Observed one weir missing from skimmer. Replace weir.
11 2 Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair No No No Observed one ladder without end caps. Replace.
12 4 Pool maintenance: inlets and other fittings in place and in good repair No No No Observed vacuum line without cap. Corrected during inspection.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No Observed >4" under gates. Maintain 4" or less.
22 6 Premises: emergency telephone provided No No No Observed phone fading in and out when connected to 911. Operator not audible. Immediate Suspension issued.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Observed flow meter installed improperly and not operating. Install according to manu. instructions and keep operational.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Observed fan not operating and no cross ventilation in chem room. Provide adequate ventilation.
27 2 Equipment room: filter backwash discharged through an air gap No No No Observed no air gap at backwash line to pit. Provide air gap.
28 2 Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted No No No Observed no shower sign. Post visible upon entrance to pool.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Observed water in restrooms at 114 F. Maintain at 110 F or below.