2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Chlorine at 0.3 ppm. Maintain at least 1.0 ppm through the chlorinator. Immediate Suspension issued. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Observed step handrail loose at pool. Repeat item. Tighten and keep in good repair. |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Pool light not secure. Gap around bottom. Tighten and maintain secure. ITS items. Ensure openings no greater than 1/2". |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Main entry door sticking on carpet when opened fully. Ensure door self-closes, self-latches. Intent to Suspend item. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Flow meter for chlorinator installed on outlet line. Required per NSF approval on inlet line. Intent to Suspend item. Flow meter is new. |