2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Chlorine at 0.2 ppm. Operator turned up chlorinator at beginning of inspection but no change in chlorine level. Maintain at least 1.0 ppm through chlorinator. Immediate Suspension issued. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Some days with chlorine levels below 1.0 ppm. No corrective actions. Provide corrective actions on log books.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Water level high in pool. Maintain water level so skimmers can operate per manufacturer instructions. .2518 |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Step handrail loose. Keep in good repair.
.2521 Install ladders per manufacturer instructions. |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
Lights not operational in swimming pool. Permit issued for night swimming with no night visit. Provide photograph documentation of sufficient lighting with no pool lights operational. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter not operational. Repair by next inspection.
.2518(g) Keep flow meter operational. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Muriatic acid stored above dry chemicals in chemical storage room. Corrected during inspection.
.2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up. |