NameLA FITNESS AND PRO RESULTS
Address12325 COPPER WAY
 
City/State/ZIP
CHARLOTTE NC 28277
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 1/6/2022
Final Score @ Grade
28
General CommentsImmediate Suspension issued for emergency phone. Pool MUST REMAIN CLOSED until suspension is lifted by Health Dept. Contact Marie Daley at 704-507-6806 when in compliance to lift suspension. Will check doors onto pool deck (self-closing, self-latching or audible alarm) and records at return visit. Changed to "E" Immediate Suspension Inspection with Andrew Lee and Lissete Del Rio No signature due to COVID

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
5 4 Water quality: daily written records of water quality and test kit kept on site No No No No records for previous 2 days. pH level, chlorine level, main drains, and water temperature must be recorded daily. *Permit item.
7 4 Pool maintenance: pool walls and floor kept clean, free of debris and in good repair No No No Scum layer observed on pool wall. .2537(14) Keep pool surface and pool floor free of debris.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No Door propped open into pool. Door onto pool deck not latching. Back door not able to be checked. .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Door must stay closed when not in use, and meet compliance at all times. *Permit item
17 4 Premises: decks unobstructed, properly drained, free of trip hazards No No No One chair on back wall within 5' of pool at time of inspection. .2522(b) Provide at least 5 ft of clear walking space around the pool at all times. Operator moved and corrected.
22 6 Premises: emergency telephone provided No No No Emergency phone not operable at time of inspection. .2530(f) Emergency phone shall remain operable. *Pool permit is suspended until emergency phone is operational. Contact Marie Daley at (704) 507-6806 when corrected.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Ventilation not working in chemical storage. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. Lights out in pump room. .2533(b) Provide sufficient lighting in pump room. Standing water in the pump room.612951 .2533(d) Pump room floor shall be kept dry and free of standing water. Chemicals stored outside of chemical storage room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
27 2 Equipment room: filter backwash discharged through an air gap No No No No air gap at backwash. Drain grate at backwash observed broken into the pit. Keep in good repair. .2513(b) Filter backwash shall be discharged through an air gap.
29 2 Dressing and sanitary facilities: required fixtures provided, clean, and in good repair No No No Hot water in restrooms is 121F. .2526(i) Water in restrooms shall not exceed 110 F.