Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameLA FITNESS AND PRO RESULTS
Address12325 COPPER WAY
 
City/State/ZIP
CHARLOTTE NC 28277
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 8/3/2021
Final Score @ Grade
24
General CommentsITS for doors onto pool deck self-closing, self-latching or audible alarm. Changed to "W" status Manager Josh Evans onsite at time of inspection. No signature due to COVID

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
2 6 Water quality: disinfectant residual provided by No No No Chlorine 0.2 ppm at time of inspection. .2535(4) Maintain chlorine at least 1.0 ppm. Operator adjusted chlorinator and corrected to 10 ppm.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No Door propped open into pool. Back door not latching or alarmed at time of inspection. .2528(a) Ground level doors shall be self-closing, self-latching or child protected by audible alarm. Door must stay closed when not in use, and meet compliance at all times..\ *30 Day Intent to Suspend (ITS). Contact Marie Daley at 704-507-6806 when item is addressed to lift ITS.
17 4 Premises: decks unobstructed, properly drained, free of trip hazards No No No Items, chairs, tables, within 5' of pool. .2522(b) Provide at least 5 ft of clear walking space around the pool at all times. Manager moved items and corrected.
22 6 Premises: emergency telephone provided No No No Emergency phone not operable at time of inspection. .2530(f) Emergency phone shall remain operable. Operator replaced phone and corrected.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Ventilation not working in chemical storage. Lights out in equipment room. Items within 3' of piping. Pool built 2010. .2533(e) Provide continuous forced ventilation or cross ventilation in pump and chemical room. Pool pump room unlocked and open at time of visit. Chemicals in equipment room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534..2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator. .2533(b) Provide sufficient lighting in pump room. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
27 2 Equipment room: filter backwash discharged through an air gap No No No No air gap at backwash. Drain grate at backwash observed broken into the pit. Keep in good repair. .2513(b) Filter backwash shall be discharged through an air gap.