| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Chlorine at 0.4 ppm. Maintain at 1.0 ppm through chlorinator. Immediate Suspension issued. |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
Pool pH at 7.0. Maintain at 7.2 to 7.8. Immediate Suspension issued. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No record keeping. Pool closed for some of time period. Maintain daily record keeping for chlorine, pH and main drain checks. Maintain weekly total alkalinity and cyanuric acid testing weekly. Permit Item. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
PDSC form with incorrect model number. CHII-NI-5F pump on form. CFII- installed. Email sent to management group to get updated form. Immediate Suspension issued.
Holes drilled into drain cover to secure to floor due to stripped holes and previously rusted screws. Additional research required prior to decision on next step for drain covers. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Staining on top steps into pool. Pool plaster does not meet LRV >50%. Plaster is dark.
.2514(c) Pool finish shall be white or light colored. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Grab rope on ring buoys degrading. Replace with USCG approved ring buoys. Immediate Suspension issued. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Grills and trash cans located outside of barrier and provides footholds. Eliminate footholds. Permit item. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Some damage to pool deck near shallow end. Offsets not greater than 1/2" and does not present cut/trip hazard. Continue to monitor and repair as needed.
Some pool furniture <6 ft. to pool edge. Maintain 6 ft. clearance around pool in all locations. Permit item. |
|
18
|
4
|
Premises: lifeguards present or warning signs posted |
No |
No
|
No |
Emergency phone signage, pool rules signage blocked by furniture. Move furniture so that signage is clearly visible upon entry to pool. Permit item. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Chlorinator could not be verified. Chlorinator shall detect flow and turn off with no flow from pump. Permit item.
No flow meter on chlorinator. Original construction. If repaired/replaced, install flow meter on inlet line to chlorinator per NSF approval. |