Water quality: pool water pH |
No |
No
|
No |
Pool pH at 7.0. Maintain at 7.2 to 7.8. Immediate Suspension issued. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Provide documentation for yearly inspections on Paddock drain covers. No records maintained. Paddock covers require yearly inspection and records maintained after 10 years of install. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
All screws rusted on one set of Paddock drain covers. Some screws rusted on other set of Paddock screws. Covers shall be installed per mfg. instructions. Once screws rusted, shall be replaced. Immediate Suspension issued. Once screws replaced, submit documentation for new screw replacement.
Vacuum line left on without cap in place. Corrected during inspection. Turned off and vacuum line cap replaced. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
One ring buoy too long. Rope cut to 45 ft. during the inspection. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
One gate with damaged plexiglass. Plexiglass required due to <45" between horizontals. Replace plexi where needed.
Observed <45" between bottom horizontal and next horizontal on perimeter fencing. Pool built 4/30/2010. Maintain 45" between horizontals. |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
Light burnt out at shallow end of pool. Repair light. Pool is not approved for night swimming. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
911 operator not audible. Breaking in and out where they could not be heard. Immediate Suspension issued. 911 shall be clearly audible at all times.
Kings III phone in place. Does not ring back to phone when number dialed. Given 30 days to repair phone so that phone number listed, when dialed, rings back to the emergency phone. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter not operational. Repair so operational. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Pump room floor wet. Keep dry.
Lights burnt out in chemical storage room and pump room. Provide adequate lighting. |