| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
.2535(10) Provide test kit capable of measuring disinfectant level, cyanuric acid and total alkalinity. Observed several expired chemicals in test kit.
.2535 (11) The pool operator shall inspect the pool at least daily and maintain written records. Observed several days of missing Chlorine and pH records in record log. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
.2514(c) Pool finish shall be white or light colored. Dark staining (algea?) on pool step furthest from gate entrance. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
.2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. Observed heavy debris inside all skimmer baskets.
.2518(k) Water level shall be maintained to assure skimmers are operable. Observed water level too high in all skimmers.
.2518(k) Surface skimmers shall be installed per manufacturer's instructions. One weir sticking located near 4 ft. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
.2521(b) Ladders shall be corrosion-resistant. Observed corrosion at bottom of handrail at steps. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. One ring buoy rope >45 ft. Corrected during inspection. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
.2537(b) All gates and doors shall be self-closing, self-latching. Observed gate nearest to grill not self-closing. ITS item.
.2528(a) Maintain 45" between bottom horizontal and next horizontal on fence and/or gate (post-May 2010). Observed less than 45" between bottom horizontal and next horizontal on gate. |
|
18
|
4
|
Premises: lifeguards present or warning signs posted |
No |
No
|
No |
.2530(c) All pool signage shall be visible upon entrance to the pool and permanently affixed. Observed pool signage not visible behind large seating. ITS item. |
|
21
|
4
|
Premises: pool and deck lighting provided at pools that operate at night |
No |
No
|
No |
.2524 For Night Swimming - provide sufficient lighting so that all parts of the pool and required deck area are visible and main drains are clearly visible. Operator not present during inspection. Pool is approved for night swimming. If continue Night Swimming is required for 2020 operating season, lighting on pool deck and inside pool must be verified. ITS item. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
.2530(f) Emergency phone shall remain operable. Observed 911 operator unable to hear EHS through the emergency phone.
Immediate suspension issued. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
.2535(6) Automatic chlorine and bromine feeder pumps shall be automatically prevented from operating when the circulation pump is not in operation. Automated feeder could not be verified at time of inspection. Operator was not present. ITS item. |