Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameVUE, THE
Address215 N PINE ST
 
City/State/ZIP
CHARLOTTE NC 28202
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 3/21/2017
Final Score @ Grade
22
General Comments15 - General Comment - Some weathering on ring buoys. Recommend replacing ring buoys. 22 - General Comment - Emergency phone somewhat muffled. Repair phone.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
5 4 Water quality: daily written records of water quality and test kit kept on site No No No Alkalinity and acid not recorded. Recorded weekly. Repeat non-compliance. Intent to Suspend issued.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Skimmers with debris under baskets. Corrected during inspection. Keep clean.
16 4 Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained No No No 2 1/2" under fence at stairwell entrance side of pool closest to emergency phone. Maintain 2" or less. Grills located next to fence on outside measuring <45" from ground to burner/side table. Eliminate foothold. Intent to Suspend issued for above items.
17 4 Premises: decks unobstructed, properly drained, free of trip hazards No No No Some minor damage to decking around skimmers. Repair damage.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Chlorinator/acid feeder does not turn off when pump turns off. Repair so that automated system detects flow and turns off. Intent to Suspend issued. Flow meter leaking. Repair/replace flow meter.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Pump room floor wet due to leak. Keep dry. No light in chemical storage room. Provide lighting.