3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
pH 7.0. .2535(1) Maintain pH at 7.2 to 7.8. - Immediate suspension item. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Inadequate record keeping. Only checking every other day in September and twice a week since then. Stopped using state sheet, no place for temperature checks on new sheet. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature. Provide weekly recordings for total alkalinity. - Intent to suspend item.
Test kit expired. .2535(10) Provide test kit capable of measuring disinfectant level, cyanuric acid and total alkalinity. - Intent to suspend item. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Pool floor dirty. .2537(14) Keep pool surface and pool floor free of debris. - Intent to suspend item. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
EcoLab automatic feeder warning light on. pH 7.0 on feeder. .2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions. - Intent to suspend item. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Door to equipment room, chemical storage room, and heater not capable of latching and locking. .2525(b) Heaters shall be equipped with thermostatic controls capable of assuring that the maximum operating temperature of heated public swimming pools other than spas does not exceed 90 degrees Fahrenheit. Such controls shall be accessible only to the operator. - Intent to suspend item. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
No light in the chemical storage room. .2534(6) Provide sufficient lighting in chemical storage room. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Light burned out in men’s restroom. .2526(m) Keep restrooms and fixtures clean and in good repair. |