Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
Logo Main Menu
Mecklenburg County Health Dept
Public Health Inspections
Select your filters and click the Search button to search for data, or click Clear to clear all filters
 
  
 

Premises Information

Return to Inspections
NameCOMFORT SUITES
Address14510 BOULDER PARK DR NORTH
 
City/State/ZIP
HUNTERSVILLE NC 28078
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 3/14/2023
Final Score @ Grade
40
General CommentsInspection conducted with hotel staff. Outer rope on ring buoy starting to fray. Recommend replacing with a new US Coast Guard approved ring buoy Emergency phone number calls back to front desk. Ensure front desk is staffed whenever the pool is open. Immediate suspension issued 2) Contact Will Harrison (704-507-6824) for re-inspection when issues have been corrected.

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
2 6 Water quality: disinfectant residual provided by No No No Free chlorine 0.4 ppm. .2535(4) Maintain chlorine at least 1.0 ppm. - Immediate suspension item.
5 4 Water quality: daily written records of water quality and test kit kept on site No No No No records since February 16th. Prior to that no records on the weekends. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity. - Intent to suspend item.
7 4 Pool maintenance: pool walls and floor kept clean, free of debris and in good repair No No No Pool floor dirty. .2537(14) Keep pool surface and pool floor free of debris. - Intent to suspend item.
8 4 Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris No No No Skimmer with toys and other debris. .2518(k) Keep skimmers free of debris so skimmers are capable of operating per manufacturer instruction. - Intent to suspend item.
11 2 Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair No No No Handrail loose. .2521 Install handrails per manufacturer instructions.
12 4 Pool maintenance: inlets and other fittings in place and in good repair No No No Missing an eyeball fitting by the ladder. .2537(8) Fittings and/or face plates shall be replaced when damaged and kept in good repair. - Intent to suspend item.
21 4 Premises: pool and deck lighting provided at pools that operate at night No No No Pool and indoor pool, roughly half of the lights were working, underwater light off as well. .2524(b) Lighting shall be sufficient to illuminate all parts of the pool, the water, the depth markers, signs, entrances, restrooms, safety equipment and the required deck area and walkways. - Intent to suspend item.
23 4 Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 No No No EcoLab chlorinator and acid feeder turned off. .2535(6) Provide NSF approved automatic chlorinator installed per manufacturer instructions.
24 4 Equipment room: approved pump, filter, and flow meter operating properly No No No Door to equipment room, chemical storage room, and heater not capable of latching and locking. .2525(b) Heaters shall be equipped with thermostatic controls capable of assuring that the maximum operating temperature of heated public swimming pools other than spas does not exceed 90 degrees Fahrenheit. Such controls shall be accessible only to the operator. - Intent to suspend item.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No No light in the chemical storage room. .2534(6) Provide sufficient lighting in chemical storage room.
28 2 Dressing and sanitary facilities: bathhouse or rest rooms accessible; shower sign posted No No No Shower handle broken. .2526(h) Shower(s) shall be provided.