2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
No free chlorine in the pool. .2535(4) Maintain chlorine at least 1.0 ppm. - Immediate suspension item. |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
pH 6.9. .2535(1) Maintain pH at 7.2 to 7.8. - Immediate suspension item. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
No records since September. .2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. - Intent to suspend item. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Pool floor dirty. .2537(14) Keep pool surface and pool floor free of debris. - Intent to suspend item. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
One weir installed backwards. .2518(k) Surface skimmers shall be installed per manufacturer's instructions. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Bottom step missing non-slip tread. .2521 Install ladders per manufacturer instructions. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Throw rope heavily knotted. Ring buoy stored out of reach of children and short adults. .2530(a) Provide US Coast Guard approved ring buoy with 15 ft throw rope. Equipment should be conveniently located. - Corrected. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemicals stored in the pump room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
No fan in the chemical storage room. .2534(3) Provide continuous forced ventilation or cross ventilation in chemical storage room.
No light in the chemical storage room. .2534(6) Provide sufficient lighting in chemical storage room.
Fan tied to the light in the pump room. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. |