6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
.2539(c) All pools, prior to permit issuance, shall provide documentation to the Department to verify suction outlet safety compliance.
Drain covers installed in pool (Aquastar 12MFxxx) do not match approved PDSC on file (Aquastar 1216101). Submit updated PDSC for approval. Immediate suspension item. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less.
Ring buoy rope too long. Operator shortened to 25’. No permit action. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
Observed chemicals in pump room. Move to designated chemical storage room. |