| CDI=Corrected During Inspection | |
R=Repeat Violation | |
VR=Verification Required | |
|
|
| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Cyanuric acid above 100 ppm. Maintain at 100 ppm or less. Intent to suspend issued. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
PDSC form with incorrect drain cover. Installed is Aquastar P12xxx drain cover. Operator provided corrected forms during inspection. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Light protruding from wall near emergency phone. Eliminate pinch hazard. Repair light to wall. Intent to suspend issued. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
One damaged skimmer basket. Replace skimmer basket. Intent to Suspend issued. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Front gate not self-closing. Repair to self-close. Intent to Suspend issued.
Window limiters missing or greater than 4" on courtyard perimeter windows. Intent to Suspend issued.
.2528(a) Ground level windows shall not open greater than 4" on to pool deck or child protected by audible alarm.
Gate hinges left on barrier next to gate that provide footholds and electrical conduit boxes located nexted to barrier provide foothold (located <45" in height). Eliminate footholds. Pool built in 2009. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter not operable on return line. Repair flow meter. Intent to Suspend issued. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Water on pump room floor and flooring not sloped to drain.
.2533(d) Pump room floor shall be kept dry and free of standing water.
Chemicals stored in pump room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Water in restrooms >120 F. Maintain at 110 F or below.
One sink in women's restroom slow draining. Repair sink drainage. |
|