Water quality: pool water pH |
No |
No
|
No |
The pH was 6.9 at time of inspection.
.2535(1) Maintain pH at 7.2 to 7.8. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Safety rope to ring buoy dry rotted. Broke during inspection.
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter not operational.
.2518(g) Flow meter be capable of measuring 1.5 times the design flow rate.
.2518(f) Provide a vacuum cap or self-closing cap for pools built after May 1, 2010. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Pump room floor area cluttered blocking walkway.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
Chemicals not stored in pump room.
.2534(3) Store all chemicals in the chemical storage room.
Observed pump room door open.
.2533(a) The equipment room door shall have a permanent lock and be kept locked when not in use by the pool operator. |