Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Cyanuric acid above 100 ppm. Maintain at 100 ppm or below. Intent to Suspend issued.
.2535 (4) Lower and maintain cyanuric acid at or below 100 ppm. |
|
6
|
6
|
Submerged suction outlets meet ASME/ANSI A112.19.8-2007. Single drains protected. (.2537, .2539) GPM= ____Field verification complete=____ |
No |
No
|
No |
PDSC form with incorrect drain covers. Does not match what was on file. Installed Aquastar 12MFxxx. Operator filled out new paperwork during inspeciton. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Some algea on pool walls. Continue to monitor green algea. Keep pool walls clean and in good repair. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Front entry gate with opening 4"x8" near latching mechanism. Intent to Suspend issued. .2528(a) Provide no openings in fence and/or gate greater than 4"x4".
Window limiters missing or greater than 4" on courtyard perimeter windows. Intent to Suspend issued.
.2528(a) Ground level windows shall not open greater than 4" on to pool deck or child protected by audible alarm.
Electrical conduit box outside pool barrier and gate hinges left on barrier next to gate that provide footholds (located <45" in height). Eliminate footholds. Pool built in 2009. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Pool furniture 4 ft. to pool edge. Maintain 6 ft. clearance around pool in all locations. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Phone number posted at pool phone for front office. Corrected to designated pool phone number during inspection. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Pool chemicals stored in equipment room. .2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Water in restrooms >120 F. Maintain at 110 F or below.
One sink in women's restroom slow draining. Repair drainage so functional.
Note: Men's restroom not viewed. No access. |
|
30
|
2
|
Dressing and sanitary facilities: approved water source, no cross connections |
No |
No
|
No |
Hose bib in pump room without backflow prevention device. Located before check valve. Provide backflow prevention device. |