5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Main drain check is missing from records.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. Operator checked main drain and corrected on records. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Automatic feeder not shutting off with pump. Flow detector in disrepair at time of inspection.
.2535(6) Automatic chlorine and bromine feeder pumps shall be automatically prevented from operating when the circulation pump is not in operation.
.2535 Automatic acid feeder shall be automatically prevented from operating when the circulation pump is not in operation.
*30 Day Intent to Suspend (TS) |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemicals in vats, being used in pump room. Items within 3' of piping/equipment. Light out in chemical room.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2534(6) Provide sufficient lighting in chemical storage room. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
Hot water in restrooms and at shower over 110 F at time of inspection. .2526(i) Water in restrooms shall not exceed 110 F. |