17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Chair within 5' of pool fixture at time of inspection.
.2522(e) Provide at least 5 ft of clear walking space around diving board, handrail, slide, or other permanent structure on a swimming pool deck. Operator moved and corrected. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
Feeder not shutting off with pump for chlorine or acid. .2535(6) Automatic chlorine and bromine feeder pumps shall be automatically prevented from operating when the circulation pump is not in operation.
.2535 Automatic acid feeder shall be automatically prevented from operating when the circulation pump is not in operation.
ITS for feeder. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Chemicals in vats, being used in pump room. Items within 3' of piping/equipment.
.2534(2) Pools constructed after April 1, 2004 shall provide a separate room for chemical storage meeting Rule.2534.
.2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Hose in backwash pit, below flood level rim. No anti-siphon device on hose at time of inspection. Hose removed from backwash. Corrected. .2513 (b) There shall be no direct physical connection between the sewer system and any drain from the swimming pool or circulation system. Overflow from the swimming pool, and discharges from the circulation system, when
discharged to the sewer system, storm drain or other approved natural drainage course, shall be discharged through a suitable air gap so as to preclude the possibility of back flow of sewage or other waste water into the swimming pool or the swimming pool piping system.
Provide backflow prevention device. |