5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Main drain checks missing from current week. Ensure recorded daily. Total alkalinity missing from November and some December. Ensure weekly record keeping for total alkalinity. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Some sand on pool floor. Keep clean. |
|
8
|
4
|
Pool maintenance: surface skimmers (with weirs, baskets and covers) or gutters clean, in good repair, and functioning properly, no floating debris |
No |
No
|
No |
Gutter popped in corner near handicap lift. Repair gutter to ensure flush so no trip hazard. Does not extend >1/2". |
|
12
|
4
|
Pool maintenance: inlets and other fittings in place and in good repair |
No |
No
|
No |
Screw in light popping out. Corrected during the inspection. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Pool furniture less than 5 ft. to pool edge. Maintain 5 ft. clearance around the pool in all locations. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
No flow meter on bromine stick feeder. Required for NSF approval. If repaired/replaced, install with flow meter per mfg. instructions. |
|
32
|
2
|
Dressing and sanitary facilities: floors smooth, slip-resistant, kept clean |
No |
No
|
No |
Floor does not appear slip-resistant in restrooms.
.2526(c) Restroom floors shall be smooth to insure cleaning and slip-resistant. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No hose bib or floor drain in restrooms. Original construction. Floor shall be sloped to drain with drain and hose bib present. |