| Violation Item
| Demerits
| Violation Description
| CDI | R | VR |
|
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Main drain checks not recorded daily. Temperature records kept under total alkalinity section. Total alkalinity not recorded. Record main drain checks, bromine, pH and temperature checks daily. Record total alkalinity weekly. Intent to Suspend issued. |
|
7
|
4
|
Pool maintenance: pool walls and floor kept clean, free of debris and in good repair |
No |
No
|
No |
Some sand on pool floor. Keep pool floor clean. Caution: Sand in pool usually indicates a broken lateral in the filter. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Ring buoy rope not attached to buoy. Corrected during the inspection. |
|
17
|
4
|
Premises: decks unobstructed, properly drained, free of trip hazards |
No |
No
|
No |
Pool furniture less than 5 ft. to pool. Maintain 5 ft. clearance around pool in all locations.
Some grout missing from deck tile. Continue to monitor and repair if worsens. May require repair in the future. Deck shall be impervious surface. |
|
23
|
4
|
Equipment room: chlorine or bromine automatic feeders that meet NSF Standard 50 |
No |
No
|
No |
No flow meter on bromine stick feeder. Required for NSF approval. If repaired/replaced, install with flow meter per mfg. instructions. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Flow meter not operable. Flow meter required due to permit restriction. Flow meter shall not exceed 420 gpm due to filters. Repair flow meter so operable and does not exceed 420 gpm. Intent to Suspend issued.
One filter not operable due to multi-port damage. When turned on, goes to backwash. All three filters shall be operable due to design flow of the pump. Intent to Suspend issued. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Pump room door left unlocked and open. Keep shut and locked when not in use.
Some water on pump room floor. Operator had been working on equipment. Keep pump room floor dry to due electrical. |
|
29
|
2
|
Dressing and sanitary facilities: required fixtures provided, clean, and in good repair |
No |
No
|
No |
One sink in women's restroom not operable. Repair so operable. |
|
32
|
2
|
Dressing and sanitary facilities: floors smooth, slip-resistant, kept clean |
No |
No
|
No |
Floor does not appear slip-resistant in restrooms.
.2526(c) Restroom floors shall be smooth to insure cleaning and slip-resistant. |
|
33
|
2
|
Dressing and sanitary facilities: hose bibbs and floor drains provided |
No |
No
|
No |
No hose bib or floor drain in restrooms. Original construction. Floor shall be sloped to drain with drain and hose bib present. |