Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Observed gaps in the log book records. Tests and records must be kept daily for chlorine, pH, main drains, equalizer line covers and once a week for Total Alkalinity and Cyanuric Acid. Cyanuric Acid must be no more than 100ppm in the pool. These tests must be done every day including weekends and holidays. Weekends are not being covered in the log book. Correct the practice and make sure all required tests are done and recored on the required intervals. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Observed one gate not to fully self-close and fully self-latch. Correct the gate, all gates must fully self-close and self-latch. |
|
22
|
6
|
Premises: emergency telephone provided |
No |
No
|
No |
Observed 911 call box to be non-functional. Call box must function, be able to accept a call, be able to contact local 911 service, and local 911 service must have the correct address for the pool and the correct call-back number for the box. Immediate Suspension issued, pool is closed to swimming. Contact C. Elmore when correction is made. -704-507-6814. |
|
27
|
2
|
Equipment room: filter backwash discharged through an air gap |
No |
No
|
No |
Observed no air gap at the backwash line. |