4
|
6
|
Water quality: water temperature of heated pool |
No |
No
|
No |
Temperature of heated pool 92.7 F at time of inspection.
.2535(12) Maintain pool temperature at 90 F or below. Operator using floating thermometer, may be difficult to read when out of range. Suggested digital thermometer. Operator added water and turned pool heater off. Digital thermometer obtained reading 88.9 F. Corrected. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
At time of inspection, ladder at end of pool loose, missing rubber stoppers.
.2521 Install ladders per manufacturer instructions. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Items within 3’ of piping and equipment in pump room. Hose bib in restroom with no antisiphon device. Vent fan in chemical room not working at time of inspection. No light in chemical room. Pool built '09. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room.
.2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room.
.2533(e) Provide continuous forced ventilation or cross ventilation in pump room.
.2534(6) Provide sufficient lighting in chemical storage room.
.2533(d) Pump room floor shall be kept dry and free of standing water. |