NameSPRINGHILL SUITES
Address12325 JOHNSTON RD
 
City/State/ZIP
CHARLOTTE NC 28277
Premise Type53 - Year-Round Swimming Pool
CountyMecklenburg
Inspection Date 2/26/2026
Final Score @ Grade
10
General CommentsMain drains expire 12/2026. Replace and submit updated PDSC form with ALL required information PRIOR to expiration to avoid permit action. Visit https://eh.mecknc.gov/pools for more information and search “Pool Documents”, pool ID 530217 for PDSC information and submit to pdsc@mecknc.gov

Violations

 
CDI=Corrected During Inspection  R=Repeat Violation  VR=Verification Required 
Violation Item Demerits Violation Description CDIRVRComments
4 6 Water quality: water temperature of heated pool No No No Temperature of heated pool 92.7 F at time of inspection. .2535(12) Maintain pool temperature at 90 F or below. Operator using floating thermometer, may be difficult to read when out of range. Suggested digital thermometer. Operator added water and turned pool heater off. Digital thermometer obtained reading 88.9 F. Corrected.
11 2 Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair No No No At time of inspection, ladder at end of pool loose, missing rubber stoppers. .2521 Install ladders per manufacturer instructions.
25 2 Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure No No No Items within 3’ of piping and equipment in pump room. Hose bib in restroom with no antisiphon device. Vent fan in chemical room not working at time of inspection. No light in chemical room. Pool built '09. .2533(c) Valves and controls shall be accessible to the pool operator at all times. Maintain 3 ft. clear walking space in pump room. .2533(g) Provide a hose bib with backflow prevention device within 50 ft. of the equipment room. .2533(e) Provide continuous forced ventilation or cross ventilation in pump room. .2534(6) Provide sufficient lighting in chemical storage room. .2533(d) Pump room floor shall be kept dry and free of standing water.