2
|
6
|
Water quality: disinfectant residual provided by |
No |
No
|
No |
Observed chlorine levels at 0.5 ppm. Maintain chlorine at least at 1.0ppm. Immediate suspension issued.
.2535(4) Maintain chlorine at least 1.0 ppm. |
|
3
|
6
|
Water quality: pool water pH |
No |
No
|
No |
Observed pH at 6.8. Maintain pH between 7.2 and 7.8. Immediate suspension issued.
.2535(1) Maintain pH at 7.2 to 7.8. |
|
5
|
4
|
Water quality: daily written records of water quality and test kit kept on site |
No |
No
|
No |
Observed no daily/weekly recording for November. Maintain required daily/weekly recordings.
.2535(11) Provide record keeping including daily records of disinfectant residual, pH, drain cover/grate inspections, pool water maintenance, and temperature, if applicable. Provide weekly recordings for cyanuric acid and total alkalinity weekly. |
|
11
|
2
|
Pool maintenance: diving equipment, ladders, steps and handrails properly placed, in good repair |
No |
No
|
No |
Observed end caps missing on one ladder. Replace end caps.
.2521 Install ladders per manufacturer instructions. |
|
15
|
6
|
Premises: body hook and ring buoy with throw rope or lifeguard with rescue tube provided and properly located |
No |
No
|
No |
Throw rope extremely brittle and in poor condition. Replace with a 45 foot throw rope. Immediate suspension issued.
.2530(a) Provide ring buoy for rope 1.5 times the width of the pool or 50 ft whichever is less. |
|
16
|
4
|
Premises: fence or barrier with self-closing, self-latching gates properly constructed and maintained |
No |
No
|
No |
Observed both gates open during inspection. One gate was not self-closing/ self- latching, repair.
.2537(b) All gates and doors shall be self-closing, self-latching. |
|
24
|
4
|
Equipment room: approved pump, filter, and flow meter operating properly |
No |
No
|
No |
Observed flow meter stuck. Repair.
.2518(g) Keep flow meter operational. |
|
25
|
2
|
Equipment room: equipment and chemicals kept in a dry, well-ventilated enclosure |
No |
No
|
No |
Observed bags of chemicals stored on the floor in chemical room. Store bags of chemicals off of the floor in chemical room.
.2534(5) Chemicals shall be stored as to prevent a reaction and permit for easy clean-up. |